Download (2.4 Mb)
DNF7 Air-Insulated Switchgear withdrawable vcb up to 40.5 kV/31,5kA/2000A
Metal-clad Switchgear type DNF7, brand Schneider Electric
Standard type:
- switchgear is small-sized armored air-insulation switchgear and can effectively save space;
- switchgear has central design and is equipped with EvoPact HVX 35 kV indoor medium-voltage withdrawable and enclosed vacuum circuit breaker Schneider Electric;
- switchgear possesses sufficient space for cable connection;
- switchgear is equipped with earth a switch that has short-circuit making capacity and quick closing function.
Drive-operated type:
- the circuit breaker and earth switch of switchgear are equipped with driver-operated device and can realize unattended transformer substation;
- the driver-operated device possesses electric machinery overload protection function and extended functions including hand operation precedence and closing interlock, and operates steadily and reliably.
Technical data
Switchgear Type | DNF7 | |
Rated voltage | kV | 40,5 |
Rated power frequency withstand voltage | kV/1 min | 95 |
Rated lighting surge withstand voltage (peak value) | kV | 185 |
Rated frequency | Hz | 50/60 |
Rated current | A | 630; 1250; 1600; 2000 |
Rated short circuit breaking current | kA | 31,5 |
Rated short time withstand current (3s) | kA | 63 |
Service type | one-sided/two-sided | |
Protection level: | ||
Shell | IP 41 | |
Between compartments | IP 21 | |
Outline dimension: | ||
W | mm | 1200 |
H | mm | 2400 |
D | mm | 2505 |
Internal ARC Classification | AFLR | |
Partition class | PM | |
Loss of Service Continuity Classification | LSC2B |
Switchgear Type DNF7 Exceptional Benefits
- manufactured by Schneider Electric;
- metal-clad switchgears is made of galvanized steel;
- metal-clad switchgears shell is divided into compartments by grounded metal partitions and has increased mechanical strength;
- thermal monitoring TH110;
- environmental monitoring CL110;
- service safety switchgear:
- presence of mechanical and electromagnetic interlocks that prevent errors during operational switching;
- design that protects against electric arc damage;
- simplicity of maintenance and repair, convenient access to the equipment and points of connection of the cables;
- use of modern equipment Schneider Electric;
- motorized drive withdrawable circuit breaker (on request);
- motor drive for earthing knife control (on request);
- low weight of new switching devices.